How to write an I/O list for a customized PLC

Whether you buy a standard PLC or have a controller built around your machine, one document drives the design: the I/O list. A good one takes a few hours to write and saves weeks of questions, redesigns and surprises at commissioning. This guide covers what to record, the details that change the hardware, and a worked example.

I/O list template. An Excel workbook with the I/O list, communication ports and machine details laid out, with example rows. It follows the same structure as this guide.

Download (Excel, 7 KB)

What an I/O list is

An I/O list has one row for every signal between the controller and the machine: each sensor, switch, valve, motor, indicator and analog instrument. For each row, record:

ColumnWhat to write
TagA short unique name, for example DI01 or AI03
What it doesIn plain words: “Guard door closed”, “Main pump running”
KindDigital input (DI), digital output (DO), analog input (AI) or analog output (AO)
Signal typeFor example 24 V DC PNP, relay, 4–20 mA or Pt100
Range or ratingThe measuring range in real units, or the load current and voltage
Connected deviceMake and model of the sensor, valve or drive, if known
NotesAnything unusual: long cable, needs isolation, high speed

Digital inputs

Push buttons, selector switches, limit switches, proximity sensors and relay contacts. For each input, note:

  • Voltage. 24 V DC is the norm in control panels. Inputs at 230 V AC are possible, but they need a different input circuit, so say so early.
  • Sensor type. Three-wire sensors are PNP (sourcing) or NPN (sinking), and the input must match. A plain contact works with either.
  • Speed. Ordinary inputs are filtered against contact bounce and noise, so a pulse of a few milliseconds can be missed. Encoders and flow-meter pulses need high-speed counter inputs; note the highest pulse frequency.

Digital outputs

Contactor coils, solenoid valves, indicator lamps, buzzers. The main choice is between relay and transistor outputs:

  • Relay outputs switch AC or DC and are isolated by nature. They are slower, and their contacts wear with every operation, so they suit loads that switch a few times a minute, not many times a second.
  • Transistor outputs switch DC only. They are fast, do not wear, and suit frequent switching and pulse outputs.

Note the voltage and current of each load. Coils and solenoids are inductive, so they need suppression: a diode across DC loads, and an RC snubber or varistor across AC loads. Outputs usually share a common terminal in groups, and each group has a total current limit as well as a per-output one.

Analog inputs

Transmitters and instruments that measure a continuous value. Common signal types:

  • 4–20 mA: the plant standard. It tolerates long cables and electrical noise, and a broken wire shows as 0 mA, which the controller can flag.
  • 0–10 V: common on drives and simple sensors, but more sensitive to cable length and noise.
  • RTD (Pt100) and thermocouples (type J, K): temperature sensors that need their own input type. Note 2, 3 or 4 wires for an RTD.
  • Load cells: millivolt-level bridge signals that need a high-resolution input with excitation. Weighing accuracy depends heavily on this input, so describe the load cell and the accuracy you need.

For every analog input, write the range in engineering units, for example “4–20 mA = 0–10 bar”. Note whether the transmitter is loop-powered (2-wire) or has its own supply, and the resolution and update rate you actually need.

Analog outputs

Speed references to VFDs, valve positioners and proportional valves, usually 4–20 mA or 0–10 V. Note the device each one drives and the range it expects.

Communication ports

List each port with what is connected to it and which side starts the conversation:

  • RS-485 with Modbus RTU, for example to read VFD status or energy meters. Note whether the controller is master or slave.
  • Ethernet with Modbus TCP, for example to an HMI panel or SCADA.
  • Other buses, such as CAN, if a device you must connect uses one.

The details that change the design

These are the questions that most often turn a “simple” controller into a redesign when they come up late:

  • Safety functions. Wire emergency stops, guard interlocks and two-hand controls through a safety relay or a safety-rated controller, as the machine’s risk assessment requires. List them so the controller can monitor their state, but do not rely on ordinary inputs to make the machine safe.
  • Spare capacity. Add 10 to 20 percent spare I/O of each kind. Commissioning nearly always finds one more sensor.
  • Supply and power budget. State the supply (often 24 V DC from the panel supply) and whether sensors and transmitters are powered from the controller.
  • Environment. Give the temperature inside the panel, not the shop floor. Mention dust, moisture, vibration and nearby noise sources such as drives or welders.
  • Operator interface. None, buttons and LEDs, a text display with keys, or a touch screen.
  • Mounting. DIN rail inside a panel, or directly on the machine.
  • Quantity. Machines per year, and for how many years. For a customized controller this matters more than anything else.
  • Programming. Whether your team writes and maintains the machine program, or needs that as part of the job.

A worked example

A small tank-filling station, as an illustration:

TagWhat it doesKindSignal typeRange or rating
DI01Start push buttonDI24 V DC, normally open contact
DI02Tank high-level switchDI24 V DC, PNP
DI03Flow meter pulsesDI, high speed24 V DC, PNP pulsesUp to 1 kHz
DI04Emergency stop status, from the safety relayDI24 V DC contactMonitoring only
DO01Pump motor contactorDORelay230 V AC coil, 0.5 A
DO02Fill valve solenoidDOTransistor, sourcing24 V DC, 1 A
AI01Tank levelAI4–20 mA, loop-powered0–3 m
AI02Product temperatureAIPt100, 3-wire0–100 °C
AO01Pump VFD speed referenceAO0–10 V0–50 Hz
COM1VFD status and fault codesRS-485Modbus RTU, controller is master9600 baud

Totals: four digital inputs, one of them high speed; two digital outputs, one relay and one transistor; two analog inputs of different types; one analog output; and one RS-485 port. Add spares, and this short table already tells a controller designer most of what they need.

Send it, even if it is incomplete

A partial list marked “not sure” is far more useful than no list. An engineer can fill the gaps with you in the technical review. To start: